OAR 918-225-0370: Exemptions for Coil-Type Water Boilers
Edition: Current OARD snapshotEffective: 1994-01-01Last verified: 2026-09-07
Coil-type water boilers, where the water can flash into steam when released directly to the atmosphere through a manually operated nozzle, are exempt from ORS 480.510 to 480.665 if the following conditions are met: (1) There is no drum, header, or other steam space; (2) No steam is generated within the coil; (3) Tubing outside diameter does not exceed one inch; (4) Pipe size does not exceed NPS 3/4; (5) Nominal water capacity does not exceed six gallons; (6) Water temperature does not exceed 350° F; (7) Adequate safety relief valves and controls are provided.
Official history and status
Statutory/Other Authority: ORS 480.560
Statutes/Other Implemented: ORS 480.560
History: BCA 36-1993, f. 12-30-93, cert. ef. 1-1-94, Renumbered from 918-225-0096 BCA 30-1991, f. & cert. ef. 9-9-91 BCA 19-1991(Temp), f. 6-14-91, cert. ef. 6-15-91