OAR 918-225-0365: Exemptions for Certain Miniature Boilers
Edition: Current OARD snapshotEffective: 1994-12-23Last verified: 2026-09-07
A miniature boiler used commercially is exempt from the requirements of ORS 480.510 to 480.665, provided the boiler: (1) Does not have more than 1.5 cubic feet of steam space; (2) Is operated at not more than 30 pounds per square inch; (3) Has a safety valve set at or below 30 pounds per square inch; and (4) Meets the safety standards adopted by any of the following laboratories as of December 23, 1994: (a) Underwriters Laboratories, Inc; (b) Edison Testing Labs; (c) Italian Instituto Superiore Per La Prevenzione E La Sicurezza Del Lavoro (ISPESL) also known as the “Italian National Standard”; or (d) Technischer Uberwachungsverein (TUV) also known as the “German National Standard.”
Official history and status
Statutory/Other Authority: ORS 480.545
Statutes/Other Implemented: ORS 480.545
History: BCD 29-1994, f. & cert. ef. 12-23-94 BCD 15-1994, f. & cert. ef. 6-14-94