OAR 918-225-0300: Exemptions for Fired Water Heaters
Edition: Current OARD snapshotEffective: 1994-01-01Last verified: 2026-09-07
Fired water heaters used exclusively for heating water for swimming pools or spas are considered pool boilers and are exempt from the requirements of ORS 480.510 to 480.665 if: (1) Units are equipped with a flow switch or pressure switch set at a minimum of 1-1/2 psig; (2) No intervening stop valves are installed on the discharge side of the unit; (3) Discharge piping is not reduced from the engineered sizing of the fired heater; (4) All units are equipped with an ASME-approved pressure relieving device set at 50 psig or lower; (5) The unit has a maximum of ten gallons capacity contained within the unit; and (6) The burner is wired in series with the circulating pump.
Official history and status
Statutory/Other Authority: ORS 480.560
Statutes/Other Implemented: ORS 480.560
History: BCA 36-1993, f. 12-30-93, cert. ef. 1-1-94, Renumbered from 918-225-0065 DC 3-1987, f. & cert. ef. 2-18-87, Renumbered from 814-025-0038 DC 7-1986, f. & cert. ef. 5-5-86