OAR 918-261-0039: Board Exemption for Products Located on the Load Side of a Listed Class 2 Transformer
Edition: Current OARD snapshotEffective: 2004-04-01Last verified: 2026-09-07
(1) An exemption from product certification is granted under ORS 479.540 for installation of Class 2 products, other than wiring, located on the load side of a listed Class 2 transformer. The exemption applies only to products that are not: (a) In a damp or wet location; (b) Located in a plenum, duct or other air-handling space; (c) Located in any area from chapter 5 of the adopted Oregon Electrical Specialty Code; or (d) Part of a protective signaling system. (2) An exemption from permitting is created for installation of Class 2 wiring located on the load side of a listed garage door controller. The exemption applies only to one- and two-family dwellings when the wiring is not part of the original wiring of the dwelling. [Publications: Publications referenced are available from the agency.]
Official history and status
Statutory/Other Authority: ORS 479.540
Statutes/Other Implemented: ORS 479.540
History: BCD 4-2004, f. 3-31-04, cert. ef. 4-1-04