OAR 333-121-0130: Fire Protection
Edition: Current OARD snapshotEffective: 2005-04-11Last verified: 2026-09-07
(1) The radiation room at a panoramic irradiator must have heat and smoke detectors. The detectors must activate an audible alarm. The alarm must be capable of alerting a person who is prepared to summon assistance promptly. The sources must automatically become fully shielded if a fire is detected. (2) The radiation room at a panoramic irradiator must be equipped with a fire extinguishing system capable of extinguishing a fire without the entry of personnel into the room. The system for the radiation room must have a shut-off valve to control flooding into unrestricted areas.
Official history and status
Statutory/Other Authority: ORS 453.675
Statutes/Other Implemented: ORS 453.675
History: PH 5-2005, f. & cert. ef. 4-11-05